Online Ups

Online Ups NM36MX1KK11 1KVA/800W
Applications
Small Computer Network
Servers Cyber Café
Banks And Offices


Salient Features
High frequency and double conversion online technology
High end Micro Controller Based
Wide Input voltage range
Advanced PFC Technology
Advanced Battery Management
Automatic Battery Charging in UPS off mode
Short Circuit and overload protection
EMI / RFI noise filter
Smart RS232 Communication with monitoring software
SNMP card slot (optional)
LCD/LED Display simultaneously
Specially designed to suit Indian power and environment conditions
Generator Compatible
Isolation Transformer (Optional)
Over Temperature Protection.
Different output Voltage settings.
Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
Static Bypass Enable or Disable.
Outlets Programmable and non programmable.
Protection from DC Fan failure.

Technical Specifications

Model
NM36MX1KK11


Capacity
1KVA / 800W


Input Voltage Range
When load < 50%, range is 118±5VAC~295±5VAC

When ± 50% load, input range is 160±5VAC~295±5VAC


Frequency
46~54Hz±0.5Hz


Phase
Single Phase


Input Power Factor
≥0.95


Output Voltage
208/220/230/240V AC


Frequency Range
50Hz ± 0.2%


THD (Liner Load)
<3%


THD (Non-Liner Load)
<5%


Overload Capability
>110% 30s turn to bypass mode;

>150%, 200ms turn to bypass


Crest Factor
3:1 (max)


Shot Circuit Protection
5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode), 5 cycles turn off inverter, provide alarm (battery mode), input fuse blown or breaker action


Waveform
Pure Sine Wave


Transfer time AC to bypass mode
4ms (typical 2.5ms)


Efficiency
≥ 85%~92%


4ms (typical 2.5ms)


Battery DC Voltage
36VDC


4ms (typical 2.5ms)


Charge Current
0.7A ~ 08A


Communication Interface
RS232; SNMP (optional)



Online Ups NM72MX2KK11 2KVA / 1600W
Applications
Small Computer Network
Servers Cyber Café
Banks And Offices


Salient Features
High frequency and double conversion online technology
High end Micro Controller Based
Wide Input voltage range
Advanced PFC Technology
Advanced Battery Management
Automatic Battery Charging in UPS off mode
Short Circuit and overload protection
EMI / RFI noise filter
Smart RS232 Communication with monitoring software
SNMP card slot (optional)
LCD/LED Display simultaneously
Specially designed to suit Indian power and environment conditions
Generator Compatible
Isolation Transformer (Optional)
Over Temperature Protection.
Different output Voltage settings.
Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
Static Bypass Enable or Disable.
Outlets Programmable and non programmable.
Protection from DC Fan failure.

Technical Specifications

Model
NM72MX2KK11


Capacity
2KVA / 1600W


Input Voltage Range
When load < 50%, range is 118±5VAC~295±5VAC

When ± 50% load, input range is 160±5VAC~295±5VAC


Frequency
46~54Hz±0.5Hz


Phase
Single Phase


Input Power Factor
≥ 0.95


Output Voltage
208/220/230/240V AC


Frequency Range
50Hz ± 0.2%


THD (Liner Load)
<3%


THD (Non-Liner Load)
<5%


Overload Capability
>110% 30s turn to bypass mode;

>150%, 200ms turn to bypass


Crest Factor
3:1 (max)


Shot Circuit Protection
5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode), 5 cycles turn off inverter, provide alarm (battery mode), input fuse blown or breaker action


Waveform
Pure Sine Wave


Transfer time AC to bypass mode
4ms (typical 2.5ms)


Efficiency
85%~92%


4ms (typical 2.5ms)


Battery DC Voltage
72VDC


4ms (typical 2.5ms)


Charge Current
0.7A ~ 08A


Communication Interface
RS232; SNMP (optional)



Online Ups NM72MX3KK11 3KVA / 2400W
Applications
Small Computer Network
Servers Cyber Café
Banks And Offices


Salient Features
High frequency and double conversion online technology
High end Micro Controller Based
Wide Input voltage range
Advanced PFC Technology
Advanced Battery Management
Automatic Battery Charging in UPS off mode
Short Circuit and overload protection
EMI / RFI noise filter
Smart RS232 Communication with monitoring software
SNMP card slot (optional)
LCD/LED Display simultaneously
Specially designed to suit Indian power and environment conditions
Generator Compatible
Isolation Transformer (Optional)
Over Temperature Protection.
Different output Voltage settings.
Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
Static Bypass Enable or Disable.
Outlets Programmable and non programmable.
Protection from DC Fan failure.

Technical Specifications

Model
NM72MX3KK11


Capacity
3KVA / 2400W


Input Voltage Range
When load < 50%, range is 118±5VAC~295±5VAC

When ± 50% load, input range is 160±5VAC~295±5VAC


Frequency
46~54Hz±0.5Hz


Phase
Single Phase


Input Power Factor
≥ 0.95


Output Voltage
209/220/230/240V AC


Frequency Range
50Hz ± 0.2%


THD (Liner Load)
<3%


THD (Non-Liner Load)
<5%


Overload Capability
>110% 30s turn to bypass mode;

>150%, 200ms turn to bypass


Crest Factor
3:1 (max)


Shot Circuit Protection
5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode), 5 cycles turn off inverter, provide alarm (battery mode), input fuse blown or breaker action


Waveform
Pure Sine Wave


Transfer time AC to bypass mode
4ms (typical 2.5ms)


Efficiency
85%~92%


4ms (typical 2.5ms)


Battery DC Voltage
72VDC


4ms (typical 2.5ms)


Charge Current
0.7A ~ 08A


Communication Interface
RS232; SNMP (optional)



SUPERMAX - SERIES - I 5KVA to 30KVA
Applications
Networking Equipment
Computer Rooms
Mission Critical Process
Bank
Office
Railways
Hospitals
Defence and Telecom Centers
all types of Single Ph. Loads


Salient Features
True online double conversion technology
High end Micro Controller
Automatic Battery charging in UPS off mode
Wide Input voltage range
Advanced Battery Management
Short circuit and overload protection
Parallel Redundant / Hot Standby. (optional)
Galvanic isolation
1 Phase in ~ 1 Phase out (upto 10KVA)
3 Phase in ~ 1 Phase out (upto 30KVA)
Specially Designed to Suit Indian Power and Environment Conditions
Generator Compatible

Technical Specifications

Model
Supermax-Series - I


Capacity
5KVA to 30KVA


Technology
Double Conversion high Freq. Switching PWM, using IGBT's


Input Voltage Range
160V AC~270V AC ±5V AC, Single Phase for upto 10KVA and 360V AC~450V AC ±5V AC, Three Phase for upto 30KVA


Frequency
45~55Hz


Phase
Single phase upto 10KVA and Three Phase from 5 to 30KVA


Generator Compatibility
Present


Output Voltage
230V Ac ±1%


Frequency Range
50Hz ± 0.5%


THD (Liner Load)
<3%


THD (Non-Liner Load)
<5%


Overload Capability
125% for 2minuted / 150% for 30Sec


Crest Factor
3:1 (max)


Shot Circuit Protection
Instant


Waveform
Pure Sine Wave


Manual Bypass
Inbuilt upto 15KVA


Static Bypass (optional)
<5ms


Inverter Efficiency
≥ 90% on rated full load


Overall Efficiency
≥ 80%


Battery DC Voltage
180 / 360 VDC


SUPERMAX - SERIES - II(3 Phase in ~ 3 Phase out) 5KVA to 30KVA
Applications
Software Centers
Mission Critical Process
Offices, Railways
Airport
Hospitals
Defence
Telecom Centers
Chemical Plants
Pharmaceutical Laboratory and all type
of three ph. Load e.g. 3 ph. motor, lifts etc.



Salient Features
True online double conversion technology
High end Micro Controller / DSP based
Automatic Battery charging in UPS off mode
Wide Input voltage range
Advanced Battery Management
Short circuit and overload protection
Hot standby. (Optional)
Galvanic isolation
3 Phase in ~ 3 Phase out
Specially designed to suit Indian power and environment conditions
Generator Compatible

Technical Specifications

Model
Supermax-Series-I(3 Phase in ~ 3 Phase out)


Capacity
5KVA to 30KVA


Technology
Double Conversion high Freq. Switching PWM, using IGBT's


Input Voltage Range
360V AC~450V AC ± 5V AC, Three


Frequency
45~55Hz


Phase
Three Phase Three Wire (compatible for phase reversal)


Generator Compatibility
Present


Output Voltage
400V AC Phase to Phase ± 3% on 100% unbalance load


Frequency Range
50Hz ± 0.5%


Phase
Three Phase Four Wire


THD (Liner Load)
<3%


THD (Non-Liner Load)
<5%


Overload Capability
125% for 2minuted / 150% for 30S


Crest Factor
3:1 (max)


Shot Circuit Protection
Instant


Waveform
Pure Sine Wave


Static Bypass (optional)
≤ 10ms


Inverter Efficiency
≥ 90% on rated full load


Overall Efficiency
≥ 80%


Battery DC Voltage
360V DC